EPA 608 Type 3 Practice Test
Focus on low-pressure centrifugal chillers: water-box freeze prevention during recovery, high-efficiency purge monitoring, and ASHRAE 15 equipment room safety.
Official target: 25 questions in 45 minutes (72% required) · 41 regulation-cited pool items · Primary text: U.S. EPA 40 CFR Part 82, Subpart F (§82.150–§82.169)
Type III (Low-Pressure Chillers)
Question 1 of 15 · Low-Pressure Chiller Table 1 Evacuation
A hospital central plant schedules a compressor overhaul on an 850-lb R-123 centrifugal chiller using a recovery unit manufactured in 2019. To what minimum Table 1 level must the chiller be evacuated before opening it?
Jump to any question (0/15 answered)
Independent preparation tool. Not affiliated with, endorsed by, or sponsored by the U.S. EPA, ESCO Group, Mainstream Engineering, or any EPA-approved certifying organization. We do not administer official exams or issue Section 608 technician cards.
Type III (Low-Pressure Chillers) blueprint and domain weights
Requires 18/25 (72%) plus passing Core.
| Exam domain | Weight | Primary citation | Tested workplace decisions |
|---|---|---|---|
| Low-Pressure Evacuation & Purge Operations | 40% | 40 CFR §82.156(a)(2)(iii) | 25 inHg / 25 mmHg absolute vs. 29 mmHg absolute thresholds and high-efficiency purge unit monitoring. |
| Chiller Freeze Prevention & Leak Testing | 35% | 40 CFR §82.156 & §82.157 | Water-box circulation during recovery, vapor charging above 36°F saturation, and controlled hot-water pressure tests. |
| Rupture Discs, Relief Valves & ASHRAE 15 | 25% | ASHRAE Standard 15 & 40 CFR §82.156 | 15 psig rupture disc limits, refrigerant monitors, SCBA alarms, and mechanical room ventilation. |
Related study charts and exam modules
Free quick-reference sheets and study guides
EPA 608 hub and sibling sections
Frequently asked questions
Why must chiller water pumps keep circulating during Type III refrigerant recovery? + -
Removing refrigerant liquid drops evaporator saturation temperature below 32°F; circulating water (or draining tubes) prevents freezing and rupturing heat exchanger tubes.
What vacuum depth applies to low-pressure chillers on post-1993 units? + -
Table 1 requires evacuating low-pressure appliances to 25 mmHg absolute (approximately 29 inHg gauge vacuum) using equipment manufactured on or after Nov 15, 1993.
At what pressure does a low-pressure chiller rupture disc open? + -
Low-pressure centrifugal chiller rupture discs are typically set to relieve at 15 psig to protect the vessel from over-pressurization during hydrostatic or hot-water leak testing.
Unlock the full EPA 608 simulator once
Pay once via Waffo Checkout. Access ends cleanly after your study window with zero recurring billing across all 41 verified items.
7-Day Cram Pass
Full EPA 608 question bank, 1:1 timed exam simulator, missed-question drill, and flashcards for 7 days. Stops automatically, with zero auto-renewal.
Focused 7-day cram window (Pass Guarantee excluded)
Get 7-Day Cram Pass30-Day Exam Pass
Full EPA 608 simulator access for 30 days plus our Conditional Pass Guarantee. One-time payment, expires automatically.
Includes Conditional Pass Guarantee (pass fee refund or 90-day extension)
Get 30-Day Exam Pass90-Day Extended Pass
Complete 90-day EPA 608 prep window with Conditional Pass Guarantee for technicians or managers studying across schedules.
Includes Conditional Pass Guarantee (pass fee refund or 90-day extension)
Get 90-Day Extended PassApplies only to 30-Day and 90-Day passes. Never covers third-party official proctor or testing center registration fees. Independent preparation tool. Not affiliated with, endorsed by, or sponsored by the U.S. EPA, ESCO Group, Mainstream Engineering, or any EPA-approved certifying organization. We do not administer official exams or issue Section 608 technician cards.
Regulatory Sources & Methodology
All practice scenarios, evacuation limits, cooking thresholds, and passing benchmarks are authored directly from public-domain federal regulations rather than recalled or proprietary test content.